DCA25USI 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #3 (07/19/11) — PAGE 19
ENGINE OPERATING PANEL
Figure 5. Engine Operating Panel
1000
2000
3000
0
R P M
OFF
W
U
V
OFF
W-U
V-W
U-V
DECREASE
INCREASE
STOP
OPERATION
(PRE-HEAT)
START
3
1
2
4
5
6
7
8
9
10
11
12
The definitions below describe the controls and functions
of the Engine Operating Panel (Figure 5).
1.
Panel Light Switch When activated will turn on control
panel light.
2. Panel Light Normally used in dark areas or at night
time. When activated, panel lights will illuminate. When
the generator is not in use be sure to turn the panel light
switch to the OFF position.
3. Oil Pressure Alarm Lamp Indicates that the oil
pressure is too low or high and will shut down the engine.
4. Oil Pressure Alarm Lamp Indicates that the water
temperature is outside of normal range and will shut
down the engine.
5. Fuel Filter Water Lever Alarm Lamp Indicates that
water level in the fuel level has risen. Drain the water in
the fuel filter strainer when this condition occurs.
6. Preheat Lamp When the ignition key is placed in
the preheat position, this lamp will illuminate to indicate
preheating of the engine glow plugs. When the lamp turns
off, this indicates that the preheat cycle is complete and
the engine can be started.
7. Ignition Switch Three position switch, stop, operation
and start. Insert ignition key to start and stop engine.
8. Oil Pressure Gauge Normal operation should be
between 28 ~71 psi (193 ~490 kPa). When starting the
generator the oil pressure may read a bit higher, but after
the engine warms up the oil pressure should return to
normal.
9. Water Temperature Gauge During normal operation
this gauge be should read between 165° F to 203° F.
10. Charging Ammeter Gauge Indicates the current
being supplied by the engine’s alternator which provides
current for generator’s control circuits and battery
charging system.
11. Fuel Gauge — Indicates amount of diesel fuel available
12. Tachometer — Indicates engine speed in RPM’s for 60
Hz operation. This meter should indicate 1800 RPM’s
when the rated load is applied. In addition a built in hour
meter will record the number of operational hours that
the generator has been in use